APC Smart-UPS RT 20kVA RM 230V SURT20KRMXLI APC Smart-UPS RT, 16 kW / 20 kVA,Input 230V / Output 230V, Interface Port DB-9 RS-232, RJ-45 10/100 Base-T, Smart-Slot, Extended runtime model, Rack Height 12 U Includes: CD with software, Rack Mounting support rails, Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card Features LCD display Dual mains input Single or three-phase input wireable Removable input/output wiring tray Rack/Tower convertible Manageable external batteries Output Output Power Capacity 16 kW / 20 kVA Max Configurable Power 16 kW / 20 kVA Nominal Output Voltage 230V Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage Efficiency at Full Load 94.00% Output Voltage Distortion Less than 5% Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Crest Factor 3 : 1 Waveform Type Sine wave Output Connections (1) Hard Wire 3-wire (H N + G) (1) Hard Wire 5-wire (3PH + N + G) (8) IEC 320 C19 (2) IEC Jumpers Efficiency at Half Load 94% Bypass Built-in Static Bypass,Internal Bypass (Automatic and Manual),Optional External Bypass Input Nominal Input Voltage 230V Input Frequency 40 - 70 Hz (auto sensing) Input Connections Hard Wire 3 wire (1PH+N+G) Hard Wire 5-wire (3PH + N + G) Input voltage range for main operations 160 - 280V Other Input Voltages 220,240 Maximum Input Current 105A Input Breaker Capacity 125A Input Total Harmonic Distortion Less than 5% for full load Batteries & Runtime Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof Included Battery Modules 4 Typical recharge time 2.50 hour(s) Replacement Battery RBC44 RBC™ Quantity 4 Nominal Battery Voltage +/-192 V (split battery referenced to neutral) Efficiency in Battery Operation 93% Typical Backup Timeat Half Load 15.3 minutes (8000 Watts) Typical Backup Timeat Full Load 4.9 minutes (16000 Watts) Runtime Chart Smart-UPS RT Extended Run Options APC Smart-UPS RT 20kVA RM 230V Communications & Management Interface Port(s) DB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot Pre-Installed SmartSlot™ Cards AP9619 Control panel Multi-function LCD status and control console Audible Alarm Audible and visible alarms : configurable delays Emergency Power Off (EPO) Yes Surge Protection and Filtering Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 Physical Maximum Height 20.98 inches (533 mm) Maximum Width 17.00 inches (432 mm) Maximum Depth 30.43 inches (773 mm) Rack Height 12U Net Weight 545.00 lbs. (247.73 kg) Shipping Weight 691.40 lbs. (314.27 kg) Shipping Height 38.98 inches (990 mm) Shipping Width 24.02 inches (610 mm) Shipping Depth 39.49 inches (1003 mm) Color Black Units per Pallet 1.00 Environmental Operating Environment 32 - 104 °F (0 - 40 °C) Operating Relative Humidity 0 - 95% Operating Elevation 0-10000 feet (0-3000 meters) Storage Temperature 5 - 113 °F (-15 - 45 °C) Storage Relative Humidity 0 - 95% Storage Elevation 0-50000 feet (0-15000 meters) Audible noise at 1 meter from surface of unit 59.00 dBA Online Thermal Dissipation 3487.00 BTU/hr Conformance Regulatory Approvals EN/IEC 62040-2,EN/IEC 62040-1-1,VDE Standard Warranty 2 years repair or replace